  Description:

Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-31: Cables with special fire performance - Single core non-sheathed cables with halogen-free thermoplastic insulation, and low emission of smoke

  Purpose

EN 50525-3-31 applies to non-sheathed single core cables insulated with halogen-free thermoplastic compound and having low emission of smoke and corrosive gases when exposed to fire. NOTE 1 Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as part of the check for absence of halogens (see Annex B of EN 50525-1). The cables are of rated voltages U0/U up to and including 450/750 V. NOTE 2 Cables rated 450/750 V may be used at 600/1 000 V when this cable is used in fixed installations with mechanical protection, within switchgear and control gear - see HD 516. For cables rated at 450/750 V there are two types, Type 1 and Type 2. Type 2 cables are required to meet a more severe test for resistance to flame propagation (EN 60332-3-24) than Type 1, and have particular suitability for installation in bunches (see also HD 516). The cables are intended for fixed wiring applications. The maximum conductor operating temperature for each of the cables in this standard is 70 °C. NOTE 3 HD 516 contains extensive guidance on the safe use of cables in this standard. This EN 50525-3-31 should be read in conjunction with EN 50525-1, which specifies general requirements.

  Publication

Wednesday 20th of April 2016

  Related Standards

EN 60811-604:2012

Low voltage (LVD) Directive (2014/35/EU)

Electric and optical fibre cables - Test methods for non-metallic materials - Part 604: Physical tests - Measurement of absence of...

EN 60811-409:2012

Low voltage (LVD) Directive (2014/35/EU)

Electric and optical fibre cables - Test methods for non-metallic materials - Part 409: Miscellaneous tests - Loss of mass test fo...

EN 60811-509:2012

Low voltage (LVD) Directive (2014/35/EU)

Electric and optical fibre cables - Test methods for non-metallic materials - Part 509: Mechanical tests - Test for resistance of ...

EN 60811-508:2012

Low voltage (LVD) Directive (2014/35/EU)

Electric and optical fibre cables - Test methods for non-metallic materials - Part 508: Mechanical tests - Pressure test at high t...

EN 60811-507:2012

Low voltage (LVD) Directive (2014/35/EU)

Electric and optical fibre cables - Test methods for non-metallic materials - Part 507: Mechanical tests - Hot set test for cross-...

EN 60811-506:2012

Low voltage (LVD) Directive (2014/35/EU)

Electric and optical fibre cables - Test methods for non-metallic materials - Part 506: Mechanical tests - Impact test at low temp...

  Stay up to date

CELAB is Notified Body No.2037 for the EMC Directive and Italian office of a Notified Body for the RED Directive.

CELAB performs voluntary inspection activities on technical construction files to check their contents.

CELAB can accomplish all the required tests in order to affix the CE-marking related to EMC, LVD, RED, MDD, machines and many others.

CLICK HERE TO GET TESTS AND INFO ON THE EN 50525-3-31:2011 STANDARD

  ACCESS

Search for a standard
GO

Register

Already a member?
Login

  OTHER APPLICATIONS

If you are interested in DO160 tests, you can give a try to our other free of charge software:
CE-Marking assistant, Version: 1.3.0